|
Heat Pumps
Heat Pump Basics
There are two common types of heat
pumps: air-source heat pumps and geothermal heat pumps
(GHPs). Either one can
keep your home warm in the winter and cool in the summer.
An air-source heat pump pulls its heat indoors from the
outdoor air in the winter and from the indoor air in the
summer. A GHP extracts heat from the indoor air when it's
hot outside, but when it's cold outside, it draws heat
into a home from the ground, which maintains a nearly constant
temperature of 50º to 60ºF.
An air-source heat pump can provide efficient heating and cooling for your
home, especially if you live in a warm climate. When properly installed, an
air-source heat pump can deliver one-and-a-half to three times more heat energy
to a home compared to the electrical energy it consumes. This is possible because
a heat pump moves heat rather than converting it from a fuel, like in combustion
heating systems.
http://www.eere.energy.gov/consumerinfo/factsheets/airheatpump.html
RETURN
TO TOP |
Heat Pumps - How They Work
You might be wondering how an air-source
heat pump uses the outdoor winter air to heat a home.
Believe it or not:
heat can be harvested from cold outdoor air down to about
40ºF. And this can be accomplished through a process
you're probably already familiar with—refrigeration.
Basically, a heat pump's refrigeration system consists of a compressor, and
two coils made of copper tubing, which are surrounded by aluminum fins to aid
heat transfer. The coils look much like the radiator in your car. Like in a
refrigerator or air-conditioner, refrigerant flows continuously through pipes,
back and forth from the outdoor coils. In the heating mode, liquid refrigerant
extracts heat from the outside coils and air, and moves it inside as it evaporates
into a gas. The indoor coils transfer heat from the refrigerant as it condenses
back into a liquid. A reversing valve, near the compressor, can change the
direction of the refrigerant flow for cooling as well as for defrosting the
outdoor coils in winter.
When outdoor temperatures fall below 40ºF, a less-efficient panel of electric
resistance coils, similar to those in your toaster, kicks in to provide indoor
heating. This is why air-source heat pumps aren't always very efficient for
heating in areas with cold winters. Fuel-burning furnaces generally can provide
a more economical way to heat homes in cooler U.S. climates.
The efficiency and performance of today's air-source heat pumps is one-and-a-half
to two times greater than those available 30 years ago. This improvement in
efficiency has resulted from technical advances and options such as:
- Thermostatic expansion valves
for more precise control of the refrigerant flow to
the indoor coil
- Variable speed blowers, which
are more efficient and can compensate for some of the
adverse effects of restricted ducts, dirty filters,
and dirty
coils
- Improved coil design
- Improved electric motor and two-speed compressor designs
- Copper tubing, grooved inside to increase surface area.
http://www.eere.energy.gov/consumerinfo/factsheets/airheatpump.html
RETURN
TO TOP |
Types Of Air Source Heat Pumps
You can use a central heat pump
to heat and cool a whole house. Most central heat pumps
are split-systems—that
is, they each have one coil indoors and one outdoors. Supply
and return ducts connect to a central fan, which is located
indoors. The fan, often called an air handler or blower,
circulates air throughout the house. The fan also usually
contains electric resistance coils (some units now have
a gas-fired furnace option). The heated or cooled air circulates
from the fan to the supply ducts, and openings in the home
called supply registers. Return registers and ductwork return the air to the fan to be heated.
Some heat pumps are packaged systems. These usually have
both coils and the fan outdoors. Heated or cooled air is
delivered to the interior from ductwork
that protrudes through a wall or roof. Another packaged system is the ductless
room heat pump. These pumps will efficiently heat or cool a room or small house
with an open floor plan. They are much more common for apartments and motel
rooms than homes. They can be installed in a window or through a hole in the
wall—wall installations being preferable for appearances sake. Through-the-wall
installations, however, sometimes aren't well insulated from inside to outside
and can have infiltration problems. When used, mini-split systems can solve
these problems.
http://www.eere.energy.gov/consumerinfo/factsheets/airheatpump.html
RETURN
TO TOP |
Selecting a Heat Pump
When selecting an air-source heat pump, consider the following
three characteristics carefully: the energy efficiency
rating, sizing, and the system's components.
Energy efficiency rating
In the United States, we rate a heat pump's energy efficiency by how many British
thermal units (Btu) of heat it moves for each watt-hour of electrical energy
it consumes. Every residential heat pump sold in this country has an EnergyGuide
Label, which features the heat pump's heating and cooling efficiency performance
rating, comparing it to other available makes and models.
The Heating Seasonal Performance Factor (HSPF)
The Heating Seasonal Performance Factor rates
both the efficiency of the compressor and the electric-resistance
elements. The HSPF gives the number of Btu harvested per
watt-hour used. The most efficient heat pumps have an HSPF
of between 8 and 10.
The Seasonal Energy Efficiency Ratio (SEER) rates a heat pump's cooling efficiency.
In general, the higher the SEER, the higher the cost. However, the energy savings
can return the higher initial investment several times during the heat pump's
life. Replacing a 1970s vintage, central heat pump (SEER = 6) with a new unit
(SEER=12) will use half the energy to provide the same amount of cooling, cutting
air-conditioning costs in half. The most efficient heat pumps have SEERs of
between 14 and 18.
You'll find the Energy Star® label—sponsored by the U.S Department
of Energy (DOE) and the U.S. Environmental Protection Agency (EPA)—on
heat pumps with an HSPF of at least 7 and a SEER of at least 12. Many new heat
pumps exceed these ratings, but looking for this label is a good way to start
shopping for one.
Sizing
When selecting a new heat pump, it's important that you determine the proper
size needed for your home. Bigger is not better. Oversizing causes the heat
pump to start and stop more frequently, which is less efficient and harder
on the components than letting it run for longer cycles. A properly sized heat
pump also will provide you with better comfort and humidity control than an
oversized one.
The heating and cooling capacity of heat pumps is measured in Btu per hour.
The cooling capacity is commonly expressed in "tons" of cooling capacity—each
ton equaling 12,000 Btu per hour. Correct sizing procedures involve complex
calculations, which are best performed by an experienced contractor, who uses
sizing methods accepted by the heat pump industry. Don't employ a contractor
who guesses the size of the heat pump needed. Rule-of-thumb sizing techniques
are generally inaccurate, often resulting in higher than necessary purchase
and annual energy costs.
System components
You and your contractor should discuss options that will help improve your
home's comfort and the economy of your heat pump. Regarding ducts, for example,
it's important to carefully consider their design and materials, as well as
the proper amount of space they require. Check your home's blueprints to see
if the architect and builder have planned adequate space for ducts and fans.
Heating and cooling contractors complain that they often have to squeeze heating
and cooling systems into spaces that are too small, resulting in constricted
ducts and inadequate airflow.
Except for packaged systems, you'll also need to select the proper type of
indoor coil for adequate summer moisture removal.
http://www.eere.energy.gov/consumerinfo/factsheets/airheatpump.html
RETURN
TO TOP |
Installing a New Heat Pump
A heat pump's performance and energy efficiency not only
depend on the selection and planning of the equipment but
also on careful installation.
Consumers and home builders alike tend to accept the lowest bid for heating
and air-conditioning work. This unfortunate choice can often leave a system
lacking 10 to 30 percent in the materials and labor necessary to optimize heat-pump
performance. Rather than just accepting the lowest bid, it's best to research
the performance records of local contractors, and get involved in the planning
and decision-making about your new heat pump system.
You can avoid most of the common comfort and performance problems from improper
installation by following these guidelines:
- Make your home as energy-efficient
as you can with proper insulation, energy-efficient
windows, and an effective air barrier, etc. Then your
contractor can install a smaller pump system with shorter
duct lengths. In an energy-efficient
home, it isn't necessary to run ducts all the way out to exterior walls
to install registers near the exterior walls.
- Install the ducts inside your home's insulation and air barrier, if
possible. Research shows that this strategy is a major energy saver.
- Insulate your ducts to R-8 if they must be located in an attic or crawl
space beyond the home's air barrier and insulation.
- Locate the outdoor unit on the north side of your home if possible.
If not, pick a shady spot. There should be no obstructions within 10 feet of
the sides with openings and the top.
- Specify that the measured air leakage through your new ducts be less
than 10 percent of your system's airflow. Air leakage of 5 percent or less is
possible with careful workmanship.
- Tell your contractor that you
want a return register in every room.
- Don't use building
cavities as ducts. Building-cavity return ducts are
notoriously leaky and often cause comfort, energy, and moisture
problems.
- Pull on ductwork after installation
to make sure it is fastened and sealed well. (Seal
duct
joints with mastic.)
http://www.eere.energy.gov/consumerinfo/factsheets/airheatpump.html
RETURN
TO TOP
|
Improving Performance
Poor installation, duct losses, and inadequate maintenance are more of a problem for heat pumps than for combustion
furnaces. A growing body of evidence suggests that most
heat pumps have significant installation or service problems
that reduce performance and efficiency.
According to a report on research funded by Energy Star? more than 50 percent
of all heat pumps have significant problems with low airflow, leaky ducts,
and incorrect refrigerant charge.
Increasing airflow in central heat pumps.
The capacity and the efficiency of a heat pump depend upon adequate airflow.
There should be about 400 to 500 cubic feet per minute (cfm) airflow for each
ton of the heat pump's air-conditioning capacity. Efficiency and performance
deteriorate if airflow is much less than 350 cfm per ton.
An ideal duct system has both a supply register and a return register for every
room. Most homes, however, have only one or two return registers for the entire
house. Air from other rooms must find its way back to these registers to be
reheated or re-cooled. Obstructions in return air are a common air circulation
problem, particularly from closed interior doors to rooms with no return-air
register.
Blockage of supply or return air ducts and registers can pressurize or depressurize
portions of the home, resulting in poor performance and increased air leakage
through the building envelope. Restrictions to airflow have the greatest impact
on the return-air side of the system, so repairs should start with the return
ducts.
Air from every supply register must have an unobstructed pathway back to a
return register. You can install louvered grilles through walls or doors, ducts
between rooms, and/or additional return ducts and registers to improve air
circulation.
Technicians can increase the airflow by cleaning the evaporator coil, increasing
fan speed, or enlarging the ducts—especially return ducts. Enlarging
ducts may seem drastic but in some cases, might be the only remedy for poor
comfort and high energy costs.
Air-sealing ducts
Measurements of heat pump performance indicate that duct leakage wastes 10
to 30 percent of the heating and/or cooling energy in a typical home. It's
one of the most severe energy problems commonly found in homes because the
leaking air is 20º to 70ºF warmer than indoor air in winter and 15?
to 30?F cooler in the summer.
Duct leakage may cause some minor comfort problems when ducts are located in
conditioned areas. But when leaky ducts are located in an attic or crawl space,
the energy loss is often large. Some of the worst duct leakage occurs at joints
between the air handler, and the main supply and return air ducts. Some main
return ducts use plywood or fiberglass duct-board boxes. These boxes frequently
leak because their joints are exposed to the duct system's highest air pressures.
Heating and air-conditioning contractors often use wall, floor, and ceiling
cavities as return ducts. These building-cavity return ducts are often accidentally
connected to an attic, crawl space, or even the outdoors, creating serious
air leakage. Fiberglass ducts and flex ducts are often installed improperly.
These ducts may also deteriorate with age, leading to significant supply-duct
leakage.
The best heating and cooling contractors have equipment to test for duct leakage.
Testing helps locate duct leaks and indicates how much duct sealing is necessary.
Do not use duct tape for sealing—its life span is very short, often less
than 6 months.
Refrigeration systems should be leak-checked at installation and during each
service call. Manufacturer's say that a technician must measure airflow prior
to checking refrigerant charge because the refrigerant measurements aren't
accurate unless airflow is correct.
http://www.eere.energy.gov/consumerinfo/factsheets/airheatpump.html
RETURN
TO TOP |
Operating a Heat Pump
Like combustion heating systems,
you control heat pumps using thermostats. If you leave
and return at regular times
everyday, you'll save money by using automatic thermostats,
which minimize energy use during the times the home is
unoccupied. However, choosing an automatic thermostat's
reactivation time requires considering the duration of
heat-pump operation necessary to restore a comfortable
temperature. During the heating season, some homeowners
also set their thermostats back 10ºF, manually or
automatically, when they leave home or go to bed.
A two-stage thermostat controls the heating. The first stage activates the
refrigeration system. If it's too cold outside for the refrigeration system
to counteract the home's heat loss, then the thermostat's second stage activates
the electric resistance coils. An outdoor thermostat will prevent the less
efficient electric resistance heat from coming on until the outdoor temperature
falls below 40?F. An outdoor thermostat also will prevent auxiliary heat from
activating when an automatic thermostat is warming the house after a set-back
period. Use setback thermostats that are only for heat pumps.
A defrost control tells the reversing valve when to
send hot refrigerant outdoors to thaw the outdoor
coil during the winter. During the 2-to-10-minute
defrost
cycle, auxiliary heat takes over, reducing the heat pump's overall efficiency
up to 10 percent. The two most common types of defrost controls are time-temperature
and demand-defrost. Time-temperature defrost controls activate defrost at
regular time intervals for set time periods, whether
there is ice on the outdoor coil
or not.
A demand-defrost control senses coil temperature or airflow through the coil,
and only activates defrost if it detects the presence of ice. Obviously,
choosing a heat pump with demand-defrost will pay a significant efficiency
dividend.
For greater efficiency, don't locate a thermostat near a heat source or cold
draft because they can cause a heat pump to operate erratically. This includes
shading thermostats from direct sunlight. Also, do not turn the thermostat
beyond the desired temperature. It will not make the heat pump heat or cool
your home any faster. It will only waste energy. Residents who duel one another
over the thermostat settings, moving it up and down to suit their different
comfort levels, cause heat pumps to operate erratically and inefficiently.
http://www.eere.energy.gov/consumerinfo/factsheets/airheatpump.html
RETURN
TO TOP
|
Maintaining and Servicing
Heat-pump performance will deteriorate without regular
maintenance
and service. The difference between the energy
consumption of a well-maintained heat pump and a severely
neglected one ranges from 10 to 25 percent.
Regular Maintenance
Either the homeowner or service technician can perform the following routine
maintenance tasks:
- Clean or replace filters regularly (every 2 to 6 months, depending on
operating time and amount of dust in the environment).
- Clean outdoor coils as often as necessary (when dirt is visible on the
outside of the coil).
- Remove plant life and debris from around the outdoor unit.
- Clean evaporator coil and condensate pan every 2 to 4 years.
- Clean the blower's fan blades.
- Clean supply and return registers and straighten their fins.
Professional Service
You should have a professional technician service
your heat pump at least every year. The technician
can:
- Inspect
ducts, filters, blower, and indoor coil for dirt and other obstructions.
- Diagnose and seal duct leakage.
- Verify adequate airflow by measurement.
- Verify correct refrigerant charge by measurement.
- Check for refrigerant leaks.
- Inspect electric terminals, and if necessary, clean and tighten connections,
and apply nonconductive coating.
- Lubricate motors, and inspect belts for tightness and wear.
- Verify correct electric control, making sure that heating is locked
out when the thermostat calls for cooling and vice versa.
- Verify correct thermostat operation.
http://www.eere.energy.gov/consumerinfo/factsheets/airheatpump.html
RETURN
TO TOP |
|
|